category Tất cả danh mục
Menu
      PSR-PS20-1NO-1NC-24DC-SC     -     Coupling relay   Phoenix Contact

PSR-PS20-1NO-1NC-24DC-SC - Coupling relay Phoenix Contact

Mã sản phẩm: 2700356

Danh mục: PHOENIX CONTACT, Switch, Measure and Monitor Phoenix Contact,

Coupling relay for SIL 3 high and low-demand applications, couples digital output signals to the I/O, 1 enabling current path, 1 confirmation current path, 1 digital signal output, safe state off applications, test pulse filter, fixed screw terminal block

Liên hệ mua hàng

Hãng sản xuất: PHOENIX CONTACT

Chất lượng: Mới 100%

Bảo hành: Chính hãng

Chứng từ: CO/CQ, hóa đơn VAT

Liên hệ(SĐT/Zalo): 0933612627

Utilization restriction
CCCex note Use in potentially explosive areas is not permitted in China.
Product type Coupling relay
Product family PSRmini
Application Safe switch off
High demand
Low demand
Ex
Relay type Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Times
Typ. starting time with Us < 100 ms (with Us when controlled via A1)
Typical release time < 35 ms (when controlled via A1)
Recovery time 500 ms
Maximum power dissipation for nominal condition 3.28 W (IL² = 36 A²)
Nominal operating mode 100% operating factor
Air clearances and creepage distances between the power circuits
Rated insulation voltage 250 V AC
Rated surge voltage/insulation Safe isolation, 6 kV reinforced insulation from control circuit, start circuit, confirmation current path, signal output to the enabling current path; 4 kV/basic insulation between all current paths and housing
Supply
Designation A1/A2
Rated control circuit supply voltage US 20.4 V DC ... 26.4 V DC
Rated control circuit supply voltage US 24 V DC -15 % / +10 %
Rated control supply current IS typ. 45 mA
Power consumption at US typ. 1.08 W
Inrush current typ. 400 mA (Δt < 10 µs at Us)
Filter time max. 2 ms (at A1-A2; test pulse width)
≥ 100 ms (at A1-A2; test pulse rate)
Protective circuit Serial protection against polarity reversal; Suppressor diode 33 V
Supply
Designation 21/A2
Diagnostic supply voltage UD 24 V DC -15 % / +10 % (21/A2)
Input current at UD 6 mA (at 21-A2 for UD; depending on load + 100 mA at M1 and 22)
Inrush current at UD typ. 2.5 A (Δt < 20 µs at UD)
Protective circuit Serial protection against polarity reversal; Suppressor diode 38 V
Relay: Enabling current path
Output description 2 N/O contacts in series, without delay, floating
Number of outputs 1 (safety-related N/O contacts: 13/14)
Contact type 1 enabling current path
Contact material AgSnO2
Switching voltage min. 12 V AC/DC
max. 250 V AC/DC (Observe the load curve)
Switching capacity min. 60 mW
Inrush current min. 3 mA
max. 6 A
Switching capacity in accordance with IEC 60947-5-1 4 A (24 V (DC13))
5 A (250 V (AC15))
Limiting continuous current 6 A (High demand)
4 A (Low demand)
Sq. Total current 36 A2 (observe derating)
Switching frequency max. 1 Hz
Mechanical service life 10x 106 cycles
Output fuse 6 A gL/gG
4 A gL/gG (for low-demand applications)
Relay: Confirmation current path
Output description 2 N/C contacts in series, without delay, not floating (reference ground: A2)
Number of outputs 1 (safety-related N/C contacts: 21/22)
Contact type 1 confirmation current path
Contact material AgCuNi, + Au
Switching voltage min. 20.4 V DC
max. 26.4 V DC
Switching capacity min. 20 mW
Inrush current min. 1 mA
max. 100 mA
Limiting continuous current 100 mA
Switching frequency max. 1 Hz
Mechanical service life 10x 106 cycles
Output fuse 150 mA Fast-blow
Signal: M1
Output description PNP
Number of outputs 1 (non-safety-related)
Voltage approx. 22 V DC (UD - 2 V)
Current max. 100 mA
Maximum inrush current 500 mA (Δt = 1 ms at Us)
Short-circuit protection no
Output fuse 150 mA fast blow
Connection technology
pluggable no
Conductor connection
Connection method Screw connection
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross-section AWG 24 ... 12
Stripping length 12 mm
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Status display 2 x green LEDs
Operating voltage display 1 x yellow LED
Error indication 1 x red LED
Width 6.8 mm
Height 93.1 mm
Depth 102.5 mm
Housing material PBT
Safety data
Stop category 0
Safety data: EN 50156
Safety Integrity Level (SIL) 3
Safety data: IEC 61508 - High demand
Designation For use in high-demand applications, the diagnostics function must be implemented via the confirmation current path.
Equipment type Type A
Safety Integrity Level (SIL) 3
Safe Failure Fraction (SFF) 99.98 %
MTBF 80.63 Years
λSU 148.96 FIT
λSD 989.32 FIT
λDU 0.20 FIT
λDD 52.58 FIT
Probability of a hazardous failure per hour (PFHD) 1.95 x 10-10 (4 A DC13; 5 A AC15; 8760 switching cycles/year)
Proof test interval 240 Months
Duration of use 240 Months
Safety data: IEC 61508 - Low demand
Equipment type Type A
Safety Integrity Level (SIL) 3
Safe Failure Fraction (SFF) 99.66 %
MTBF 63 Years
λSU 1579 FIT
λSD 0 FIT
λDU 5.392 FIT
λDD 0 FIT
Probability of a hazardous failure on demand (PFDAVG) 1.27 x 10-4
2.36 x 10-5 (for proof test interval = 1 year)
Proof test interval 72 Months
Duration of use 240 Months
Ambient conditions
Degree of protection IP20
Min. degree of protection of inst. location IP54
Ambient temperature (operation) -40 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
Shock 15g
Vibration (operation) 10 Hz ... 150 Hz, 2g
ATEX
Identification  II 3 G Ex nA nC IIC T4 Gc
Certificate DEMKO 14 ATEX 1284X
IECEx
Identification Ex nA nC IIC T4 Gc
Certificate IECEx ULD 14.0003X
UL, USA/Canada
Identification cULus
Certificate E140324
UL, USA/Canada
Identification Class I, Zone 2, AEx nA nC IIC T4 / Ex nA nC IIC Gc T4 X
Class I, Div. 2, Groups A, B, C, D, T4
Certificate E360692
DNV
Identification C, EMC2
Certificate 11253-14 HH
CE
Certificate CE-compliant
Environmental simulation test
Identification ISA-S71.04
Note G3
Air clearances and creepage distances between the power circuits
Standards/regulations EN 60664-1, EN 60079-15
Mounting type DIN rail mounting
Assembly instructions See derating curve
Mounting position vertical, horizontal, with front of module upward
Connection method Screw connection

Sản phẩm thịnh hành

Máy nén Embraco NTX6238U 843JA72 2172W

Máy nén Embraco NTX6238U 843JA72 2172W

Mã SP: 843JA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6238U 843JA72 2446W

Máy nén Embraco NTX6238U 843JA72 2446W

Mã SP: 843JA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6238U 843JA72 2735W

Máy nén Embraco NTX6238U 843JA72 2735W

Mã SP: 843JA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6238U 843JA72 2841W

Máy nén Embraco NTX6238U 843JA72 2841W

Mã SP: 843JA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6233U 843FA72 1868W

Máy nén Embraco NTX6233U 843FA72 1868W

Mã SP: 843FA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6233U 843FA72 2088W

Máy nén Embraco NTX6233U 843FA72 2088W

Mã SP: 843FA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6233U 843FA72 2348W

Máy nén Embraco NTX6233U 843FA72 2348W

Mã SP: 843FA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6233U 843FA72 2425W

Máy nén Embraco NTX6233U 843FA72 2425W

Mã SP: 843FA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6225UV 843HD72 1702W

Máy nén Embraco NTX6225UV 843HD72 1702W

Mã SP: 843HD72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6225UV 843HD72 1978W

Máy nén Embraco NTX6225UV 843HD72 1978W

Mã SP: 843HD72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6225UV 843HD72 2161W

Máy nén Embraco NTX6225UV 843HD72 2161W

Mã SP: 843HD72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6225UV 843HD72 2236W

Máy nén Embraco NTX6225UV 843HD72 2236W

Mã SP: 843HD72

Thương hiệu: Embraco

Xuất xứ: