Primary-switched TRIO POWER power supply for DIN rail mounting, input: 1-phase, output: 5 V DC/10 A

Liên hệ mua hàng

Hãng sản xuất: PHOENIX CONTACT

Chất lượng: Mới 100%

Bảo hành: Chính hãng

Chứng từ: CO/CQ, hóa đơn VAT

Liên hệ(SĐT/Zalo): 0933612627

Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC (Derating < 90 V AC: 2.5 %/K)
Derating < 90 V AC (2.5 %/V)
Input voltage range AC 85 V AC ... 264 V AC (Derating < 90 V AC: 2.5 %/K)
Electric strength, max. 300 V AC
Voltage type of supply voltage AC
Inrush current < 30 A
Inrush current integral (I2t) < 1.9 A2s
AC frequency range 45 Hz ... 65 Hz
Mains buffering time > 40 ms (120 V AC)
> 180 ms (230 V AC)
Current consumption 1 A (120 V AC)
0.5 A (230 V AC)
Nominal power consumption 131.4 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.48
Typical response time < 1 s
Permissible backup fuse B6 B10 B16
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
Efficiency > 80 % (230 V AC)
Output characteristic U/I
Nominal output voltage 5 V DC ±1 %
Setting range of the output voltage (USet) 4.5 V DC ... 6 V DC (> 12 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (-25 °C ... 55 °C)
Derating 55 °C ... 70 °C (2.5%/K)
Feedback voltage resistance approx. 9 V DC
Protection against overvoltage at the output (OVP) < 9 V DC
Max. capacitive load unlimited
Active current limitation Approx. 12 A (in the event of a short-circuit)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 60 mVPP
Output power 50 W
Peak switching voltages nominal load < 70 mVPP
Maximum no-load power dissipation 1.5 W
Power loss nominal load max. 13.5 W
Rise time < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Input
Connection method Screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5
Tightening torque, min 0.4 Nm
Tightening torque max 0.5 Nm
Output
Connection method Screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5
Tightening torque, min 0.4 Nm
Tightening torque max 0.5 Nm
Types of signaling LED
Signal output
Status display "DC OK" LED green
Note on status display UOUT < 0.9 x UN: LED flashing
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (routine test)
Insulation voltage input / PE 2 kV AC (type test)
2 kV AC (routine test)
Product type Power supply
Product family TRIO POWER
MTBF (IEC 61709, SN 29500) > 500000 h
Insulation characteristics
Protection class I
Overvoltage category III
Degree of pollution 2
Width 40 mm
Height 130 mm
Depth 115 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm
Mounting type DIN rail mounting
Assembly instructions alignable: horizontally 0 mm, vertically 50 mm
Mounting position horizontal DIN rail NS 35, EN 60715
With protective coating No
Color aluminium
Housing material Metal
Type of housing Steel sheet, zinc-plated
Side element version Aluminum
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 15g in all directions in acc. with IEC 60068-2-27
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Rail applications EN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
EN 61558-2-17
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 50178
Standard – Safety extra-low voltage EN 60950-1 (SELV)
EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard - Safety of transformers EN 61558-2-17
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
Conformity/Approvals
SIL in accordance with IEC 61508 0
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
Standards/regulations EN 61000-4-2
Housing Level 3
Electrostatic discharge
Contact discharge 6 kV
Discharge in air 8 kV
Comments Criterion B
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 3 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (level 4 - asymmetrical: conductor to ground)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
Comments Criterion B
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
Input/Output Level 3 - asymmetrical
Frequency range 10 kHz ... 80 MHz
Comments Criterion A
Voltage 10 V
Voltage dips
Standards/regulations EN 61000-4-11
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential

Sản phẩm thịnh hành

Máy nén Embraco NTX6238U 843JA72 2172W

Máy nén Embraco NTX6238U 843JA72 2172W

Mã SP: 843JA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6238U 843JA72 2446W

Máy nén Embraco NTX6238U 843JA72 2446W

Mã SP: 843JA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6238U 843JA72 2735W

Máy nén Embraco NTX6238U 843JA72 2735W

Mã SP: 843JA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6238U 843JA72 2841W

Máy nén Embraco NTX6238U 843JA72 2841W

Mã SP: 843JA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6233U 843FA72 1868W

Máy nén Embraco NTX6233U 843FA72 1868W

Mã SP: 843FA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6233U 843FA72 2088W

Máy nén Embraco NTX6233U 843FA72 2088W

Mã SP: 843FA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6233U 843FA72 2348W

Máy nén Embraco NTX6233U 843FA72 2348W

Mã SP: 843FA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6233U 843FA72 2425W

Máy nén Embraco NTX6233U 843FA72 2425W

Mã SP: 843FA72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6225UV 843HD72 1702W

Máy nén Embraco NTX6225UV 843HD72 1702W

Mã SP: 843HD72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6225UV 843HD72 1978W

Máy nén Embraco NTX6225UV 843HD72 1978W

Mã SP: 843HD72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6225UV 843HD72 2161W

Máy nén Embraco NTX6225UV 843HD72 2161W

Mã SP: 843HD72

Thương hiệu: Embraco

Xuất xứ:

Máy nén Embraco NTX6225UV 843HD72 2236W

Máy nén Embraco NTX6225UV 843HD72 2236W

Mã SP: 843HD72

Thương hiệu: Embraco

Xuất xứ: